China Electrical Power Transformer manufacturer

Electrical High Voltage Switchgear Enclosed Ring Main Unit RMU Switchgear

Product Details:
Place of Origin: China
Brand Name: HENGFENGYOU
Certification: ISO IEC CB COC KEMA SNI SABS CCC
Model Number: KYN28A-12
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: 200-20000/piece
Packaging Details: wooden case
Delivery Time: 30 days
Payment Terms: LC T/T
Supply Ability: 5000 piece/year
Contact Now

Detail Information

Model Number: KYN28A-12 Type: Metal Clad
Rated Frequency: AC 50Hz (60Hz) Rated Current(A): 630, 1250, 1600, 2500, 3510, 4000
Customized: OEM/ODM Order Acceptable Application: Power Transmission Or Distribution
Product Name: Electrical Kyn28 12 Switchgear 11kv
High Light:

switchgear control panel

,

metal clad switchgear

Product Description

KYN28-12 Medium Voltage Switchgear

 

 

KYN28-12 (GZS1) indoor metal-fitted mid-shift open type switchgear (hereinafter referred to as the switch cabinet) is a three-phase ac 50Hz indoor power distribution unit, which is used to receive and distribute 3-12kv network power and to control, protect and monitor the circuit.The product can be installed on the panel of the relay chamber of various types of microcomputer type integrated relay protection devices, and can achieve intelligent control of the system, with remote control, telemetry, remote communication and remote control functions, can bus with communication interface to control the field network.It also has the function of preventing the wrong operation of the circuit breaker, preventing the trolley from pushing and pulling with load, preventing the electrifying closing grounding switch, preventing the grounding switch from sending electricity at the grounding position and preventing the electrifying interval from entering by mistake, which is referred to as "five defense".

 

AC metal closed type shift switch cabinet is a three-phase ac 50HZ indoor device metal closed switch equipment. Is used in power plants, substation system rated voltage 35kV, rated maximum current 2000A maximum voltage no more than 40.5kV single bus or single bus sectionalized sets of distribution equipment.
This switch device meets the requirements of DL/ t404-91, IEC298, GB3906 and other standards, and has the functions of preventing wrong operation of circuit breaker, pushing and pulling handcart with load, grounding line, power transmission with grounding line and accidental charging interval (referred to as "five precautions").

 

Structural Features

Kyn28-12 metal-armored high voltage switchgear adopts intermediate structure, which saves about 50% of the circuit breaker room and facilitates cable installation.The primary circuit switch is installed on the kola car, which is easy to be interchanged with the size trolley.Due to the armored construction, the components are installed in an earthing compartment separated by a metal partition.The protection grade of switch cabinet is IP4X.Vacuum circuit breaker with permanent magnet mechanism can be equipped with vacuum circuit breaker VS1, VD4, ZN63, etc.The switch cabinet can be connected with the protection system, with the function of "four remote control", realizing the automation of the distribution station.

Electrical High Voltage Switchgear Enclosed Ring Main Unit RMU Switchgear 0

 

 
Item Unit Parameters
Rated voltage KV 3, 7.2, 12
Rated current A 630,1250,1600,2500,3150,4000*
Rated short circuit breaking current KA 25, 31.5, 40
Rated short circuit switching current 63, 80, 100
Rated short-yime withstand current(4s) 25, 31.5, 40
Rated peak withstand current 63, 80, 100
Rated frequency Hz 50
Rated insulation level 1 min power frequency withstand voltage KV 42
Lighting impulse withstand voltage 75
control circuit voltages AC V 110, 220, 380
DC V 110, 220
Protection degree   Housing IP4X , cubicle and circuit breaker IP2X when door is open

 

 

Order information

Schematic diagram of main circuit or electrical schematic diagram
Arrangement and layout
Model, specification and quantity of main components.
Incoming and outgoing wire method and cable specification, etc
If bus connection is required between the devices, bus connection and height from the ground shall be provided.

 

 

Electrical High Voltage Switchgear Enclosed Ring Main Unit RMU Switchgear 1