China Electrical Power Transformer manufacturer

Electric 50kva 100kva Oil Immersed Transformer Three Phase Copper Winding

Product Details:
Place of Origin: China
Brand Name: HENGFENGYOU
Certification: ISO IEC CB COC KEMA SNI SABS CCC
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: 200-200000/piece
Packaging Details: wooden case
Delivery Time: 15 DAYS
Payment Terms: LC T/T
Supply Ability: 5000 pieces/year
Contact Now

Detail Information

Model Number: S-11 Phase: Three
Standard: GB1094-1996 Application: Electric
Material: Copper Winding Usage: Electronic
Keywords: Distribution Power Transformer Rated Voltage: 30-2500KV
Vector Group:: Dyn11,Dyn5,Yyno Or Others CORPORATION::: KPLC/REA/PEC
Phase:: Single Or Three Phase CERTIFICATION:: Type Test Report/CESI/ CTQC
High Light:

three phase oil immersed transformer

,

oil immersed distribution transformer

Product Description

ONAN 50kva 100kva transformer 400kva 1500kva 2500kva transformer

 

 

Production Overview

1. A multilayer cylinder structure is used for all high voltage windings in order to improve the voltage

    impulse distribution of winding.

2. For the capacity range of medium voltage windings is from 30kVA to 2000kVA, the cylinder type

    or spiral structure is used to ensure the high mechanical strength, ampere lure distribution and

    excellent short-circuits proof performance.

3. The securing structure is set in the transformer body, which is used for ensuring that no

    displacement will occur during the transportation;meanwhile, the turnbuckles are mounted in

    fasteners, which is for assuring that fasteners will not be loose during the long term operation.

4. Corrugated tanks are used in the transformer for replacing the conservator. The tank enclosure

    and rim are completely sealed by welding or bolting up, which prolongs the service life of

    transformer oil.

5. The transformer surface are painted with primer and finish coats after degreasing derusting, and 

     phosphorizing; which can meet the special operation requirements in metallurgic and

     petrochemical industries, as well as, in moist and dirty places.

6. The press relief valves, signal thermometers, and gas relays are equipped in the oil tank of

     hermetically sealed transformer in order to the standard requirements for safe operation. The

     transformers are attractive and competitive due to the compact shape, excellent and design,

     maintenance-free.

    

 

Electric 50kva 100kva Oil Immersed Transformer Three Phase Copper Winding 0

 

Main Technical Parameters for 10KV level S9-M/S10-M/S11- M Series three-phase full-sealed non-excitaiton-tap-changing distribbution transformer
Rated
Power
(kva)
High
Voltage
(kv)
H.V.Tap
range
Low
Voltage
(kv)
Connection
symbol
Short
Circuit
Impendence
(%)
No-load loss(W) On-load loss(W) No load
current
(%)
S9 S10 S11 S9 S10 S11
30 6
6.3
10
10.5
11
±5%
±2x2.5%
0.4 Dyn11
Yyn0
4 130 110 100 600 600 600 2.1
50 170 150 130 870 870 870 2
63 200 180 150 1040 1040 1040 1.9
80 250 200 180 1250 1250 1250 1.8
100 290 230 200 1500 1500 1500 1.6
125 340 270 240 1800 1800 1800 1.5
160 400 310 280 2200 2200 2200 1.4
200 480 380 340 2600 2600 2600 1.2
250 560 460 400 3050 3050 3050 1.2
315 670 540 480 3650 3650 3650 1.1
400 800 650 570 4300 4300 4300 1
500 960 780 680 5150 5150 5150 1
630 4.5 1200 920 810 6200 6200 6200 0.9
800 1400 1120 980 7500 7500 7500 0.8
1000 1700 1320 1150 10300 10300 10300 0.7
1250 1950 1560 1360 12000 12000 12000 0.6
1600 2400 1880 1640 14500 14500 14500 0.6
2000 5 2830 2270 1940 17140 17140 17140 0.6
2500 3350 2690 2300 20260 20260 20260 0.5