Product Details:
|
|
Place of Origin: | China |
---|---|
Brand Name: | HENGFENGYOU |
Certification: | ISO IEC CB COC KEMA SNI SABS CCC |
Model Number: | SCB12 |
Payment & Shipping Terms:
|
|
Minimum Order Quantity: | 1 |
Price: | 200-200000/piece |
Packaging Details: | wood pack |
Delivery Time: | 15 DAYS |
Payment Terms: | LC T/T |
Supply Ability: | 5000 pieces/year |
Detail Information |
|||
Usage: | Power Electronic Distribution Transformer | Coil Number: | Double Winding |
---|---|---|---|
Phase: | Three/ Single | Rated Capacity: | 30-3000kva,2500kVA |
Product Name: | 3 Phase Dry Type Electrical Transformer 300kva | Material: | EXPOY RESIN,Copper Or Aluminum |
Efficiency: | High Efficiency | ||
High Light: | cast resin dry type transformer,power distribution transformer |
Product Description
Product Characteristics:
Less consumption, low local discharge, low noise, strong heat dissipation, capable of 120% rated load running under forced air cooling conditions.
For its good moisture, proof performance, it can run normally under 100% humidity and cab be put into operation without pre-drying after stop.
It is safe, fire-proof and free of polution, so it can be erected in load centre directly.
It is equipped with perfect temperature protection and control system to provide reliable guarantee for safe running of transformer.
Iron core: the iron core adopts imposed high magnetic conductivity high quality cold rolled steel sheet in45 degree inclined step joining. It adopts special square tube drawplate structure and core post it bound with insulation tape. The surface is coated with special resin coating to prevent moisture and rust so as to reduce no load consumption, no load current and iron core noise effectively.
High voltage coil: F/H grade insulation
Low voltage coil
Cold device of breeze: Normally, adopts natural air-cooling. If use forced air for cooling, the output power can be run 120% of rated power. Including thermometer for automatic start and stop so as to ensure a constant cooling effect under condition of rated load running.
Low voltage connecting terminal busbar.
Features:
Note: Due to continuous product improvement, the dimensions provided in this sample are for reference only. If necessary, our company can design and produce according to user requirements. Please contact the company in time.
Model |
SCB10-500/10 |
Capacity |
500 KVA |
Primary Voltage |
10KV , 11KV |
Secondary Voltage |
0.4 KV |
Rated current(H.V.) |
28.87A |
Rated current (L.V.) |
721.7 A |
Vector Group |
DYN11 |
Insulation & Heatproof Class |
F |
Max.temperature rising |
100K |
Short-circuit impedance |
4.10 % |
phase |
3 |
Frequency |
50Hz |
Cooling Method |
AN / AF |
Net Weight |
1810Kgs |
35KV dry type power transformer with off-load tap changer |
|||||||||
Rated capacity (KVA) |
Rated Voltage(KV) |
Coupling group |
|
Loss(W) |
No-load current(%) |
Noise (B) |
|||
HV |
Tap change |
LV |
Impedance voltage(%) |
N0-load |
Load |
|
|
||
800 |
35 or 38.5 |
±5% or ±2×2.5% |
3.15,6 ,6.3,10 10.5 or 11 |
Yyn0 Dyn11 |
6 |
2220 |
8180 |
0.6 |
50 |
1000 |
2640 |
9480 |
52 |
||||||
1250 |
3090 |
11210 |
|||||||
1600 |
3640 |
13440 |
0.5 |
53 |
|||||
2000 |
7 |
4180 |
15830 |
54 |
|||||
2500 |
4800 |
18970 |
56 |
||||||
3150 |
8 |
5960 |
21280 |
0.4 |
|||||
4000 |
6930 |
25570 |
55 |
||||||
5000 |
8270 |
30350 |
58 |
||||||
6300 |
9780 |
35460 |
0.3 |
||||||
8000 |
9 |
11200 |
40000 |
||||||
10000 |
12800 |
48250 |
|||||||
12500 |
15560 |
56080 |
0.2 |
60 |
|||||
16000 |
19110 |
65980 |
61 |
||||||
20000 |
10 |
22670 |
74230 |
62 |
·Order instructions:
1. The customer needs provide main parameters of the transformer (input and output voltage, capacity, loss, etc.)
2. Other customer requirements
Enter Your Message