China Electrical Power Transformer manufacturer

KYN28 12kV Medium Voltage draw out Switchgear With Circuit Breaker

Product Details:
Place of Origin: China
Brand Name: HENGFENGYOU
Certification: ISO IEC CB COC KEMA SNI SABS CCC
Model Number: KYN28
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: 200-20000/piece
Packaging Details: wooden case
Delivery Time: 30 days
Payment Terms: LC T/T
Supply Ability: 5000 piece/year
Contact Now

Detail Information

Model Number: KYN28-24 Type: Sealed
Standard: Medium Voltage Feature: Practical And Durable
Product Name: Metal-clad Switchgear Rated Voltage: 12KV /24KV
Quality: High Quality
High Light:

mv switchgear panel

,

medium voltage cabinet

Product Description

High voltage  electrical panel for substation model KYN28-12

 

                                KYN28 12kV Medium Voltage draw out Switchgear With Circuit Breaker 0

 

 

Overview:

 

This equipment is indoor metal armoring with drawable switchgear (hereafter refer to as switchgear). With 3.6~12kv three phase AC 50Hz single bus bar and the single bus bar subsection system's complete electricity distribution equipment is used in the power plant, small and medium-sized generator power transmission, industry and mining business power distribution as well as electrical industry system's second transformer substation's electric take-over, power transmission and large-scale high pressure motor starting and so on. The purpose is to control, protect and monitor. This switch equipment is up to the standard of IEC298, GB3906 and can prevent the charge from pushing and pulling the breaker, from opening and closing the breaker, from insulation withelectricity by mistaken, from earthed switch closing the breaker, from opening the switch's interlock when it with electricity mistakenly. It can not only use with VS1 vacuum circuit breaker, but with ABB Corporation's VD4 vacuum circuit breaker. It is indeed a kind of power distribution equipment with superior performance

 

Service conditions
a. Ambient temperature: Maximum temperature:+40℃ Minimum temperature: -15℃
b. Ambient humidity: Daily average RH no more than 95%;Monthly average RH no more than 90%
c. Altitude no higher than 2500m;
d. The air around without any pollution of duty,smoke,ercode or flammable air,steam or salty fog;

 

Features:


The switch cabinet is metal-clad. Its structure design accords with the standards GB3906-91, IEC298, DL404 and DL402. The crust structure is made of steel plates by means of bending and welding, which are joined by bolts. The hand buggy panel is the door of cabinet. The bosom of switch cabinet is divided into a breaker chamber, a main bus bar chamber, a cable chamber and a relay chamber by metal partitions. The degree of protection of the entire crust and compartments is IP2X equally. All the metal structures are connected to ground reliably. All the compartments of main circuit system have pressure release channels for independent exhaust.

KYN28 12kV Medium Voltage draw out Switchgear With Circuit Breaker 1

Technical Data

 

Item Unit Data
Rated Voltage kV 3.6,7.2,12
Rated Frequency Hz 50
Rated Current of Circuit Breaker A 630,1250,1600,2000,2500,3150
Rated Voltage of Switchgear A 630,1250,1600,2000,2500,3150
Rated short-time withstand current (4s) kA 16,20,25,31.5,40,50
Rated Peak Withstand Current (Peak Value) kA 40,50,63,80,100,125
Rated Short-circuit Breaking Current kA 16,20,25,31.5,40,50
Rated Short- circuit Closing Current kA 40,50,63,80,100,125
1min Power Frequency Withstands Voltage kV 24, 32, 42
Lightning Withstands Voltage , Rated Insulation Leve kV 40, 60, 75
Protection Grade Shell is IP4X, Shell is IP2X when compartment and circuit breaker doors are open

 

Cabinet outline dimensions(mm)(not including door)

Height Width Depth
2300 800 1800
2300 1000 1800

 

 

KYN28 12kV Medium Voltage draw out Switchgear With Circuit Breaker 2  

 

 

KYN28 12kV Medium Voltage draw out Switchgear With Circuit Breaker 3

Get in touch with us

Enter Your Message