China Electrical Power Transformer manufacturer

400-800KVA Dry Type Transformer Cast Resin Transformer

Product Details:
Place of Origin: China
Brand Name: HENGFENGYOU
Certification: ISO IEC CB COC KEMA SNI SABS CCC
Model Number: SCB10
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: 500-30000
Packaging Details: wooden case
Delivery Time: 15 DAYS
Payment Terms: LC T/T
Supply Ability: 5000 pieces/year
Contact Now

Detail Information

Material: Aluminum Or Copper Usage: Single-phase Transformer, Rectifier Transformer, Combined Transformer, Power Transformer, Distribution Transformer
Capacity: 100.125.160.200.250.315.400.500.630.800.1000 HS Code: 85043190
Product Name: Dry Type Transformer Certificate: CE,ISO,CQC,SABS,3C
High Light:

cast resin dry type transformer

,

dry cast resin transformers

Product Description

Dry type transformer

400-800KVA Dry Type Transformer Cast Resin Transformer 0

SCB Dry Type power distribution transformer

 

Product Description

 

1. Application

1). Our power transformers are especially suitable for installation in draw-out type or fixing type switchgears as well as for power plants, substation, self-consumption transformers, power distribution, transmitter system, earthing system, community power supply system, subway, or those places where small space, fire-control, moisture-proof, are needed. Those up to 10kV can be installed in 650 ~ 1200 mm wide switchgear, up to 20kV in a 1000mm wide switchgear and 35kV in 1400 ~ 1600 mm wide switchgear.

2).Our series reactors are suitable for a power system of 6~10kV.They are connected serially with high voltage parallel capacitor group to depress a wave deformation in the system.

 

2.Technical Parameters

1).Rated Primary Voltage: 6kV up to 35kV
2).Rated Secondary Voltage: 0.4kV
3).Rated Capacity: 3kVA up to 2500kVA
4).Rated Short-time P. F. Withstand Voltage (r.m.s.) (kV): 20, 25, 35, 50, 70
5).Rated Lightning Impulse Withstand Voltage (Peak) (kV): 60, 75, 125, 170
6).Phase No.: single phase or three phases
7).The Highest Temperature Rise of Windings: 100K
8).Insulation Class: F
9).Cooling Mode: AN or FN
10).Enclosure Protection: IP00, IP20 or custom specified
11).Connection Symbol: Yyn0, Dyn11or II0 or custom specified
12).HV Tapping Range (%): ±5 or ±2×2.5

 

3. Main Features

1).Low loss, low noise, high operation efficiency
2).High ability of protection against short circuit
3).High mechanical strength
4).Pre-galvanized steel frame, flame-resistant, against corrosion
5).With outstanding fire-proof capability: the epoxy resin is difficult to flame and self-extinguished. So it won’t lead to the second disasters, such as an explosion.
6).Cast epoxy resin with high dielectric strength 18~22kV/mm in vacuum process
7).Superior in environmental performance: the epoxy resin is very stable, moisture-proof and dust-proof. It enables dry-type power transformers to run with high reliability under abominable environment.

8) With theimpeccable temperature control and indicating system, dry-type power transformers can be maintenance free. And this offers a great reduction of operation cost.
9).With small volume, light and convenient for installation and alignment
10).No need of a separated room

 

 

4. Materials

1).Insulation Material: epoxy resin
2).Winding Material: Aluminum wire or high quality enameled copper wire (foil winding is available for power transformer)
3).Core: core lamination, low loss, cold rolled grain oriented silicon steel

4.This products is especially suitable to be mounted in the movable or firm switch cabinet, whose width is 650-1200mm. SC10-6(10) (IV) is small,fire-proof and wet-proof.

5.The highest temperature rise of the products’ windings is 100K, their insulation class is F class, and their cooling mode is AN.


Application
SC(B) Series DRY EPOXY RESIN DISTRIBUTION POWER TRANSFORMER is widely applied in hotels, high buildings, business centers, residence community, gymnasium, Petrochemical plant, airport, harbor, metro, mine, drillic.

 

Technical data

 

Type

Rated

capacity

(KVA)

Connection

groupgrade

Voltagecombination(KV)

Noloadloss

(W)

loadloss(W)

DyYy

No-load

current(%)

Short-circuit

resistance(%)

HighvoltageTappingrang eLowvoltage
SC12-30 30

YynO

.

Dyn11

10

6.3

6

土5%

+2x2.5%

+x2.5%

0.4 150 710 2.3 4.0
SC12-50 50 215 1000 2.2
SC12-80 80 295 1380 1.7
SC12-100 100 320 1570 1.7
SC12-125 125 375 1850 1.5
SC(B)12-160 160 430 2130 1.5
SC(B)12-200 200 495 2530 1.3
SC(B)12-250 250 575 2760 1.3
SC(B)12-315 315 705 3470 1.1
SC(B)12--400 400 785 3990 1.1
SC(B)12-500 500 930 4880 1.1
SC(B)12-630 630 1070 5880 0.9
SC(B)12-630 630 1040 5960 0.9  
SC(B)12-800 800 1215 6960 0.9
SC(B)12-1000 1000 1415 8130 0.9
SC(B)12-1250 1250 1670 9690 0.9
SC(B)12-1600 1600 1960 11730 0.9
SC(B)12-2000 2000 2440 14450 0.7
SC(B)12-2500 2500 2880 17170 0.7

 

 

Product details

 

 

400-800KVA Dry Type Transformer Cast Resin Transformer 1

Points to note

 

1.working condition

* Device types: indoor type

* Normal environment conditions of use: the elevation not more than 1000 m

* Environmental highest temperature + 40℃, minimum-25 ℃

* The special environment conditions of use: elevation of more than 1000 m

* Environmental highest temperature + 40 ℃, minimum-45 ℃. (when you order details)

* Mounting ambicnt: no corrosive gas, no obvious dirt environment

 

2.applicable  standard

* IEC60076 power transformer

* IEC723 dry power transformer

* GB6450-1986 dry power transformer

* GB/R1094-1996 power transformer

* GB4208-1993 outer shell protect grade(IP code)

 

400-800KVA Dry Type Transformer Cast Resin Transformer 2

 

Qualification Centre

 

All products of the company have passed the national type test like CCC, CQC , CTQC and other

national mandatory product certification, and has a perfect quality, occupational health and

environmental management system certification system. Our products have passed ISO9001, 2000

and other international quality system certification.

 

 

400-800KVA Dry Type Transformer Cast Resin Transformer 3

 

 

SCOPE of application

 

None of the dry-type transformers we see today are installed in a separate, tightly enclosed room, as in

the oil-immersed type, but only in a relatively dry and clean room. In addition to this, it is also very convenient

to transport or carry, no matter what kind of transport vehicles, trains, cars or other non-motor vehicles can be,

but it is best to keep the car dry, clean and the product itself in good packaging. Practice has proved that really

good products will always be more and more marketable. As dry-type transformers have very good fire-proof

performance and are easy to install and maintain, they are also used more and more widely Especially in the

modern commercial downtown, residential areas, hospitals, airports, stations, subways, theaters, schools,

public places and other places with high requirements on fire protection.

 

 

400-800KVA Dry Type Transformer Cast Resin Transformer 4

 

400-800KVA Dry Type Transformer Cast Resin Transformer 5 

Get in touch with us

Enter Your Message